MY HOME: Project and installation guide - page 582

Catalog
MyHOME
AXOLUTE catalog
myhome - BUS SCS
Automation
H4671M2
H4678
3475
Item
Actuators and flush mounted actuators/dimmers
H4671M2
actuator/control with 2 independent relays - for
single, double and mixed loads: 2 A resistive, 2 A for
filament lamps, 500 W for motor reducers, 2 A cos
ϕ
0.5
for ferromagnetic transformers, and 70 W for
fluorescent lamps - logic relay interlock via the
configuration. The device may also be configured to
manage a remote actuator – 2 modules
H4671/1
1 relay actuator with control-key - for single
load: 6 A resistive or filament lamps,
2 A cos
ϕ
0,5 for ferromagnetic transformers and 150 W
fluorescent lamps - to be completed with
2-module key covers for single or double function
H4678
dimmer actuator for filament lamps and
ferromagnetic transformers - 60 – 300 VA 230 Va.c.
– to be completed with one 2-module key cover for
single or double function - 2 modules
Basic module actuators
3475
1 relay actuator - for single loads: 2 A
incandescence lamps and 2 A
cos
ϕ
0.5 for ferromagnetic transformers – suitable
for installation in ceiling light cups or
inside flush- mounted boxes, behind control
devices.
3476
1 relay actuator - for single loads: 2 A
resistive or incandescence lamps and 2 A
cos
ϕ
0.5 for ferromagnetic transformers
– input suitable for a traditional
NO contact pushbutton
White
color device
NOTE:
Neutral item
Tech
color device
Anthracite
color device
Item
ACTUATORS FOR SHUTTER MANAGEMENT
H4661M2
flush mounted 2 module actuator with 2 internal relays
and 4 pushbuttons suitable for operation in
combination with H4660M2 control devices for the
management of shutters. In addition to monostable
and bistable UP/DOWN functions the actuator presets
the shutters in a stored position (PRESET)
F401
as above - with 3 pushbuttons - 2 DIN
controllable loads (230 Va.c. 50/60 Hz)
Actuators
Type
Energy saving
filament and
LED lamps
Linear fluorescent
lamps
1)
Compact fluorescent
lamps
Electronic
transformers
3)
Ferromagnetic
transformers
2) 3)
Motor reducers for
shutters
4)
H4671M2
2 A
460W
70W
Max. 2 lamps
0.3 A
70W
70W
Max. 2 lamps
0.3 A
70W
2 A cosφ 0.5
460 VA
2 A
460W
H4671/1
6 A
1380W
150W
Max. 3 lamps
0.65 A
150W
150W
Max. 3 lamps
0.65 A
150W
2 A cosφ 0.5
460VA
-
-
H4678
0.25 - 1.30 A
60 - 300W
-
-
-
-
-
-
-
-
0.25 - 1.30 A
60 - 300 VA
-
-
3475
3476
2 A
460W
40W
Max 1 lamp
-
-
40W
Max 1 lamp
-
-
2 A cosφ 0.5
460VA
-
-
H4661M2
F401
-
-
-
-
-
-
2 A 250Va.c.
Notes:
1) Power factor corrected fluorescent lamps, energy saving lamps, discharge lamps.
2) In order to calculated the actual power of the load connected to the actuator, it will be necessary to take into account the transformer performance. For example, when connecting a dimmer to a 100VA
ferromagnetic transformer with 0.8 performance, the actual load power will be 125VA.
3) The transformer must be loaded at its rated power, or in any case never below 90% of its rated power. It will be preferable to use a single transformer, rather than several transformers in parallel.
For example, it will be preferable to use one single 250VA transformer with 5 x 50W spotlights connected, rather than using 5 x 50VA transformers in parallel, with one 50W spotlight each.
4) The
symbol shown on the actuators refers to the shutter motor reducers.
570
1...,572,573,574,575,576,577,578,579,580,581 583,584,585,586,587,588,589,590,591,592,...1181
Powered by FlippingBook